Rough Carpentry
GOODIER BUILDERS Limited Warranty
Some floor and stair squeaks are unavoidable. Although GOODIER BUILDERS does not warrant against floor squeaks, a reasonable effort will be made to correct them.
Floor Deflection
Floors will deflect (bend) when walked on. This will be more noticeable next to hutches, bookcases, pianos, chairs, and other heavy furniture. This is not a structural deficiency and GOODIER BUILDERS will take no action for this occurrence.
Floor Level
Floors will be level to within ¼ inch within any 32-inch distance as measured perpendicular to any ridge or indentation. GOODIER BUILDERS will correct floor slope that exceeds this measurement.
Plumb Walls
GOODIER BUILDERS will correct walls that are out of plumb more than ½ inch in an 8-foot vertical distance or walls that are bowed more than ½ inch in any 32-inch horizontal measurement.
Rafters or Roof Ridge Beams
GOODIER BUILDERS will correct rafters or roof ridge beam bows that are bowed greater than 1 inch in 8 feet.
Roof Sheathing
GOODIER BUILDERS will correct roof sheathing that appears "wavy" or bowed, when the bow is in excess of ½ inch in 2 feet.